One of our reader's asked if a PanelView800 can connect to a 5380.
I did a little research and here's what I found:
The latest manual (2018) for the PV800 states:
"CompactLogix 5370 L1 controller is supported only in PanelView 800 terminals with firmware revision 3.011 or later. CompactLogix 5370 L2 and L3 controllers are supported only in PanelView 800 terminals with firmware revision 4.012 or later. Connected Components Workbench Release 9 or later software is also required."
https://literature.rockwellautomation.com/idc/groups/literature/documents/um/2711r-um001_-en-e.pdf
And the knowbase states:
"The PanelView 800, 2711R, does not support the 5069 and 5380 series controllers."
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1036663/loc/en_US
So as of today it looks like the PV800 does not support the 5380, but the good news is that it does seem to now support all 5370's (initially I believe it only supported the L1.
Questions? Comments? Please post them below :-)
Shawn
Today's Automation News Roundup. To get the full news show join our membership program at https://TheAutomationBlog.com/join
Automation News Roundup for Thursday June 27, 2024. To watch the full #AutomationMorningShow become a member at YouTube.com/InsightsIA/join, or TheAutomationBlog.com/memberships
Question of the Week for Friday September 13, 2024: Studio Designer Tag Values, and Save vs. Upload. Please consider giving this episode a Like, Sub, and Share! To catch the full weekly Q & A show, become a member at https://TheAutomationBlog.com/join or https://YouTube.com/InsightsIA/join
https://theautomationblog.com/automation-q-a-for-september-13-2024/
Get the latest Industrial Automation #News from the all of the major vendors in this morning’s Automation News Shows from #TheAutomationBlog:
https://theautomationblog.com/automation-news-for-september-12-2024/
This week I meet up with Nick Rosner of @SchneiderNA to discuss their new #Altivar #Solar #ATV320 VSD in this episode of #TheAutomationPodcast: